COLD-CHAIN MAINTENANCE FEEDBACK 1 FEEDBACK ON REPAIR AND MAINTENANCE FROM THE FIELD AND Imp
COLD-CHAIN MAINTENANCE FEEDBACK 10 'Foster' Generator Panel T3 potentiometer turned both ways slightly & reset,it worked so also GK- OK
COLD-CHAIN MAINTENANCE FEEDBACK 11 'Foster' Generator Panel 4.Generator panel Wiring/ component burnt 1.Amritsar 2.Vadodara 3.Akola 4.Ernak
COLD-CHAIN MAINTENANCE FEEDBACK 12 'Foster' Generator Panel 6.Nasik Stop solenoid coil burnt Replaced- OK 6.Automatic charging
COLD-CHAIN MAINTENANCE FEEDBACK 13 5.Ajmer 6.Gandhinagar 7.Akola Dirt & lubricant formed paste,gears jammed. Chart speed slow covers 2 hours
COLD-CHAIN MAINTENANCE FEEDBACK 14 'Huurre' Cooling Unit 13.Moradabad Mechanical jam contactor similar to NK of 'Foster' is sui
COLD-CHAIN MAINTENANCE FEEDBACK 15 'Huurre' Cooling Unit 2.Rajkot Leak from non-return valve on charging tube Valve not sitting properly
COLD-CHAIN MAINTENANCE FEEDBACK 16 'Huurre' Control panel(for petrol engine) 1.Mains power not extended to the units 1.Pune 2.Trivandr
COLD-CHAIN MAINTENANCE FEEDBACK 17 'Huurre' Control panel(for petrol engine 3.generator starts & stops on 'manual'but not on
COLD-CHAIN MAINTENANCE FEEDBACK 18 'Foster' V.M.Diesel engine 5.Oil pressure decreases after about 2 hours running 1.Phulbani 2.Vadodara Im
COLD-CHAIN MAINTENANCE FEEDBACK 19 'Huurre' petrol Engine (Honda G-400) 1.Starting trouble 1.Trivandrum 2.Japiur & several other
COLD-CHAIN MAINTENANCE FEEDBACK 2 Foreword…… The refreshers training courses on maintenance & repair of WIC electrical systems, repair of Gener
COLD-CHAIN MAINTENANCE FEEDBACK 20 'Huurre' petrol Engine (Honda G-400) 7.Speed low on load 1.Visakhap-attanam No load speed-OK. Speed low
COLD-CHAIN MAINTENANCE FEEDBACK 21 Power Supply (MAINS 2.Ernakulum 3.Kozikode 4.Gurgaon Maharashtra ,A.P.& U.P. Fluctuations (150-250 V)
COLD-CHAIN MAINTENANCE FEEDBACK 22 'Vestfrost'MK-140/142 ILRs 3.Filter /capillary blocked in some new units Orissa Bihar Rajastan This is m
COLD-CHAIN MAINTENANCE FEEDBACK 23 ILRs & FREEZERs # Try inserting a capacitor(40-60 µF,220V)between No.11 & 13 of starting device. Knock the
COLD-CHAIN MAINTENANCE FEEDBACK 24 other end of the above cable is to be connected to the points 11 &12 of the 'new' panel. SUGGESTION
COLD-CHAIN MAINTENANCE FEEDBACK 25 SUGGESTION #8 The reason of fuse S1 blowing off in 'Foster'generator panel is mostly due to any of the 3
COLD-CHAIN MAINTENANCE FEEDBACK 3 COLD CHAIN MAINTENANCE- 'FEED-BACK' COMPONENT FAULT LOCATION OBSERVATION /FINDING ACTIONS/ SUGGESTIONS
COLD-CHAIN MAINTENANCE FEEDBACK 4 'Foster' (WIC) Cooling unit 2.Compressor defective 1.Balasore 1.Noisy Transit damage. taken out compres
COLD-CHAIN MAINTENANCE FEEDBACK 5 'Foster' (WIC) Cooling unit 4. Condenser fan-motor jammed. 1.Vadodara 2.Phulbani 3.Balasore 4.Parabhani 5
COLD-CHAIN MAINTENANCE FEEDBACK 6 5.Bikaner 6.Merrut 7.Bhopal (WIF) 8.Almorah 9.Bhuj 10.Ajmer 11.Faizabad 12.Bhagalpur 13.Tirunelvelly 14
COLD-CHAIN MAINTENANCE FEEDBACK 7 11.HP/LP pressostat defect 1.Vadodara Did not trip on low pressure when drier was choked & pr.wa
COLD-CHAIN MAINTENANCE FEEDBACK 8 2.MCB tripping 1.Gurgaon 2.Kota MCB trips off after about one hour & becomes hot(old-panel)
COLD-CHAIN MAINTENANCE FEEDBACK 9 # Try to find locally available two-way switch with off position. 6. Contactor defect 1.Bhopal (WIF) One unit no