Rangehood installation
electrolux e:line rangehoods rangehoodinstallation/installationsequence5
Installation sequence
1. Using a spirit level mark a vertical centre line on the wall
where the hood is to be positioned, and a horizontal line
at the hood base position (refer diagram bottom left).
NOTE: The height of the underside of the hood body must be a
minimum of 600mm above an electric cooktop & 650mm above a
gas cook top and a maximum height of 800mm (see table right).
Distance from hood base to top of hob
hob type minimum* maximum
gas 650mm 800mm
electric 600mm 800mm
* If the instructions of the hob specify a greater distance than the
minimum above, then that shall be the minimum height for installation
2. Markthelocationforthewallandceilingbracketxing
points above the hood base using the hood base as the
reference point (refer diagram left).
3. Install wall and ceiling mounting brackets with suitable
screws(tosupportatotalweightof30kg)tothewallatthe
positions marked in diagram left.
4. Removetheprotectiveplasticlmfromthehoodbody
and hang hood on the mounting brackets then secure at
theanti-tiltlocationsasindicatedindiagramleft.
Depending on the preferred installation/ducting mode,
followstep5aor5bbelow.
5a.Recirculating mode (Fig. a). Using the centre line,
secure the ceiling mount bracket to the wall using
suitablescrews.AttachtherecirculatingT-piece
(optionalkitAR600RKformodelsERCM9010and
ERCE9020,orAR600RKGformodelERCG9030)to
the ceiling mount bracket. Install flexible pipe between
T-pieceandfantransitionoutlet.Usecabletiesor
suitableducttapetosecureexiblepipetoT-piece.
NOTE: When installed in recirculation mode, it is recommended
to use a carbon filter (included in recirculation kit AR600RK for
models ERCM9010AS and ERCE9020AS, or recirculation kit
AR600RKG for model ERCG9030AS, refer to page 9) to prevent
odours being emitted back into the room.
OR
5b.Ducted mode (Fig. b). The canopy rangehood has been
supplied with flexible exhaust pipe and duct transition
piece,alternativelya150mmdia.non-combustibleue
pipe can be used. Continue the centre line to the ceiling.
Attach the ceiling mount bracket on the centre line. Fit
preferred flue pipe to the fan transition duct.