SERVICE MANUAL MIDEA AIRCONDITIONER DC INVERTER SPLIT WALL-MOUNTED TYPE MSC-09HRDN1-QD0(E) MSC-12HRDN1-QC6(E) MSH-09HRDN1-QD0(E) MS

Seite 2 - CONTENTS

7 3.2 Outdoor Unit MOC-09HDN1-QD0(E) MOC-12HDN1-QC6(E)

Seite 3

8 4. Specification Indoor MSC-09HRDN1-QD0(E) MSC-12HRDN1-QC6(E) Outdoor MOC-09HDN1-QD0(E) MOC-12HDN1-QC6(E) Power supply Ph-V-Hz 1,220-240V~,50Hz 1

Seite 4 - 1. Precaution

9 Indoor MSH-09HRDN1-QD0(E) MSH-12HRDN1-QC6(E) Outdoor MOC-09HDN1-QD0(E) MOC-12HDN1-QC6(E) Power supply Ph-V-Hz 1,220-240V~,50Hz 1, 220-240V~, 50H

Seite 5 -  Operational

105. Refrigerant cycle diagram

Seite 6

11 6. Wiring diagram 6.1 Indoor Unit MSC-09HRDN1-QD0(E) MSC-12HRDN1-QC6(E) MSH-09HRDN1-QD0(E) MSH-12HRDN1-QC6(E)

Seite 7 - 2. Function

126.2 Outdoor Unit MOC-09HDN1-QD0(E) MOC-12HDN1-QC6(E)

Seite 8

137. Installation details 7.1 Wrench torque sheet for installation Outside diameter Torque mm inch Kgf.m Ф6.35 1/4 1.8 Ф9.52 3/8 4.2 Ф12.

Seite 9 - 3. Dimension

147.4 Air purging of the piping and indoor unit Required tools: Hexagonal wrench; adjustable wrench; torque wrenches, wrench to hold the joints

Seite 10 - 3.2 Outdoor Unit

157.5 Pumping down (Re-installation) Procedure 1. Confirm that both the 2-way and 3-way valves are set to the opened position. Remove the valve

Seite 11 - 4. Specification

167.6 Re-air purging (Re-installation) Procedure: 1. Confirm that both the 2-way and 3-way valves are set to the closed position. 2. Connect th

Seite 12

CONTENTS 1. Precaution ...

Seite 13 - 5. Refrigerant cycle diagram

177.7 Balance refrigerant of the 2-way, 3-way valves Procedure: 1. Confirm that both the 2-way and 3-way valves are set to the open position. 2

Seite 14 - 6. Wiring diagram

187.8 Evacuation Procedure: 1. Connect the vacuum pump to the charge set’s centre hose. 2. Evacuation for approximately one hour. Confirm that

Seite 15 - 6.2 Outdoor Unit

197.9 Gas charging Procedure: 1. Connect the charge hose to the charging cylinder. Connect the charge hose which you disconnected from the vacu

Seite 16 - 7. Installation details

208. Operation characteristics 8.1 MSC-09HRDN1-QD0(E) Heating Capacity(KW) Piping Length Characteristics(Heating) Piping Length (m) 2.7 2.6 2.4

Seite 17

218.2 MSC-12HRDN1-QC6(E) Remark: Indoor room temperature: 20℃ Indoor fan speed: High Pipe length: 5m Cooling C

Seite 18

228.3 MSH-09HRDN1-QD0(E) Cooling Capacity(KW) Piping Length Characteristics(Heating) Piping Length (m) 2.7 2.6 2.4 2.5 2.8 2.9 3.0 10 11 12 1

Seite 19

238.4 MSH-12HRDN1-QC6(E) Cooling Capacity(KW) Piping Length Characteristics(Cooling) Piping Length (m) 3.32 3.26 3.14 3.20 3.38 3.44 3.50 3.08

Seite 20

249. Electronic function 9.1 Abbreviation T1: Indoor ambient temperature T2: Pipe temperature of indoor heat exchanger T3: Pipe tempera

Seite 21 - 7.8 Evacuation

259.2.2 LED display control function. Pressing “LED display” button on remote controller will turn off all displays on indoor unit, while

Seite 22 - 7.9 Gas charging

269.4.3 The action of auto fan in fan-only mode is the same as auto fan in cooling mode with 24℃ setting temperature. 9.5 Cooling Mo

Seite 23 - 8. Operation characteristics

9.9 Forced operation function...

Seite 24 - 8.2 MSC-12HRDN1-QC6(E)

27controller 6 times or more within 10 seconds(make sure indoor unit receives these signals), the machine will turn into rating capacity test mod

Seite 25 - 8.3 MSH-09HRDN1-QD0(E)

28 2) If the compressor stops caused by room temperature rising, indoor fan will be forced to run 127 seconds with breeze. During this period, ant

Seite 26 - 8.4 MSH-12HRDN1-QC6(E)

29J1 on on off off J2 on off on off ∆Tcon(℃) 0 -4 -2 0 9.7.4 Outdoor unit current control in heating mode. Remark:

Seite 27 - 9. Electronic function

309.7.7 Defrosting action. 9.7.8 Rating capacity test function. 1) Set the indoor unit with remote controller as: high fan, 30℃ in heating

Seite 28 - 9.4 Fan-Only Mode

319.9 Forced operation function 9.9.1 Forced cooling and auto function can carry out with a touch button. In these two modes, the machine can

Seite 29 - 9.5 Cooling Mode

329.13.3 Operation process in sleep mode is as follow: 1) After pressing ECONOMIC or SLEEP button on controller, the machine will turn into slee

Seite 30 - 9.7 Heating mode

3310. Troubleshooting Safety Because of there are capacitors in PCB and relative circuit in outdoor unit, even shut down the po

Seite 31

3410.1 Indoor Unit Error Display Display LED STATUS E0 EEPROM parameter error E1 Indoor / outdoor units communication protection E2 Zero-cro

Seite 32

35 LED1 LED4 LED5 LED6

Seite 33 - 9.8 Auto mode function

3610.3 Diagnosis and Solution 10.3.1 E0(EEPROM parameter error) error diagnosis and solution 10.3.2 E1(indoor / outdoor units communicat

Seite 34 - 9.13 Sleep function mode

1 1. Precaution 1.1 Safety Precaution  To prevent injury to the user or other people and property damage, the following instructions must be fol

Seite 35

3710.3.4 E3(indoor fan speed out of control) diagnosis and solution 10.3.5 E5(Open or short circuit of outdoor temperature sensor) diagnosi

Seite 36 - 10. Troubleshooting

3810.3.8 P1(over voltage or too low voltage protection) diagnosis and solution. 10.3.9 P2(temperature protection of compressor top) diagno

Seite 37

3910.4 Key parts checking. 10.4.1. Compressor checking (Model: DA108X1C-20FZ3). Measure the resistance value of each winding

Seite 38

4010.4.5 Temperature Sensors. Room temp.(T1) sensor, Indoor coil temp.(T2) sensor, Outdoor coi

Seite 39

41 UPDATE EXPLANATION:::: V1.1 29th, Jan., 2007 Revised by Alex Jiang & Jim Xu

Seite 40

2 arrives. There is risk of property damage, failure of product, or electric shock.  Do not open the inlet grill of the product during operation. (

Seite 41

3 your skin or clothes, wash it well with clean water. Do not use the remote of the batteries have leaked. The chemical in batteries could cause bur

Seite 42 - 10.4 Key parts checking

4 2. Function When the power supply is interrupted and then restore, the air conditioners automatically restore the previous function setting. Tele

Seite 43

5 It protects the valves and prevents water from dripping. The unit has 3 mins delay between continuously ON/OFF operations. Outdoor unit Power

Seite 44 - UPDATE EXPLANATION:

6 3. Dimension 3.1 Indoor Unit MSC-09HRDN1-QD0(E) MSC-12HRDN1-QC6(E) MSH-09HRDN1-QD0(E) MSH-12HRDN1-QC6(E)