1. Preliminary instructions
Note about the A.C. power
According to the EN 60204-1:1997 standard, the machine is provided for AC supplies
corresponding to the extracted caracteristics below :
4.3.2 AC supplies
Voltage:
Steady state voltage: from 0.9 to 1.1 of nominal voltage.
Frequency:
from 0.99 to 1.01 of nominal frequency continuously.
from 0.98 to 1.02 short time.
Harmonics:
Harmonic distorsion not to exceed 10 % of the total r.m.s. voltage between live
conductors for the sum of the second through to the fi fth harmonic. An additional 2 %
of the total r.m.s. voltage between live conductors for the sum of the sixth through to
the 30th harmonic is permissible.
Voltage unbalance:
Neither the voltage of the negative sequence component nor the voltage of the zero
sequence component in three-phase supplies shall exceed 2 % of the positive
sequence component.
Voltage interruption:
Supply interrupted or at zero voltage for not more than 3 ms at any random time in the
supply cycle. There shall be more than 1s between successive interruptions.
Voltage dips:
Voltage dips shall not exceed 20 % of the peak voltage of the supply for more than one
cycle. There shall be more than 1 second between successive dips.